loa-den-chong-chay-no-bexcs110-l2-d1xc1x10f-omni-directional-alarm-horn-led-beacon-e2s-vietnam-stc-vietnam.png

STExC1X05F Alarm Horn & Xenon Strobe

117dB(A) horn & 5 Joule Xenon. The STExC1X05F is a high output alarm horn sounder with re-entrant flare horn combined with a 500,000cd Xenon strobe beacon. The robust IP66 316L stainless steel enclosure ensures the STExC1X05F is suitable for all IECEx & ATEX Zone 1, 2, 21 & 22 explosion proof signaling applications.

The alarm horn & Xenon strobe allow simultaneous or independent operation. Featuring 64 first stage/channel alarm sounds, the alarm tone frequencies for the first 2 stages are independently selectable. Each of the available 4 stage/channels can be remotely triggered e.g. via an external relay.

Specification

 
Alarm Horn:
Maximum output: 117dB(A) @ 1 metre [108dB(A) @ 10ft/3m]
Nominal output: 113dB(A) @ 1m +/- 3dB - Tone 2 [104dB(A) @ 10ft/3m]
No. of tones: 64 (UKOOA / PFEER compliant)
No. of stages: 4
Volume control: Adjustable -12dB(A)
Effective range: 125m/410ft @ 1KHz
Supply Voltages: 24Vdc; 115Vac; 230Vac
Stage switching: DC units: negative or positive
AC units: common supply line
Strobe Beacon:
Energy: 5 Joules (5Ws)
Flash rates: Option 1: 1Hz (60 fpm)
Option 2: 1.5Hz (90 fpm)
Option 3: Double Strike
Peak Candela: 500,000 cd - calculated from energy (J)
Eff. Intensity: 250 cd - calculated from energy (J)
Peak Candela: 46,976 cd* - measured ref. to I.E.S.
Eff. Intensity: 143 cd* - measured ref. to I.E.S.
Lens colours: Amber, Blue, Clear, Green, Magenta, Red & Yellow
Tube life : Emissions are reduced to 70% after 8 million flashes
General:
Ingress protection: EN60529: IP66
Enclosure matl: 316L Stainless Steel
Enclosure finish: Chromated & powder coated
Colour: RAL3000 Red
Cable entries: 3 x M20 ISO (2 x stopping plugs supplied)
Adaptors to M25, 1/2" & 3/4" NPT can be specified
Terminals: 0.5 - 2.5mm² (20-14 AWG)
Enclosure volume: <2 litres
Line monitoring: Blocking diode included
EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor
or diode (DC versions) can be fitted
Grounding stud: M5
Temperature range: -50° to +70°C (-58°F to +158°F)
Relative humidity: 95% - Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist
Weight: 7.45kg/16.42lbs

Current Consumption

Voltage: Range: Alarm Horn Xenon Strobe Combined
12V dc 10-14Vdc 146mA 678mA 824mA
24V dc 20-28Vdc 185mA 323mA 508mA
48V dc 42-54Vdc 138mA 198mA 336mA
230V ac 220-240Vac
50/60Hz
21mA 79mA 106mA
Nominal current. Alarm horn sounder: Tone 2, Xenon Strobe: 1Hz Flash Rate

Part Codes

Version: Part code:
Product type: STExC1X05
Horn type: F Flare re-entrant horn
Voltage: DC012
DC024
DC048
AC230
12V dc
24V dc
48V dc
230V ac
Cable Entry Type:[e]






Note:
A
B
C
D
E
F
G
3 x M20x1.5mm
2 x 1/2" NPT - adaptors
2 x 3/4" NPT - adaptors
2 x M25x1.5mm - adaptors
1 x 1/2" NPT - adaptor
1 x 3/4" NPT - adaptor
1 x M25x1.5mm - adaptor
M20 stopping plugs for unused entries supplied
Adaptor/Stopping
plug material: [m]
B
N
S
Brass
Nickel Plated
Stainless Steel (standard)
Bracket/Guard material: [s] 1
2
3
4
A2 304 Stainless Steel
A4 316 Stainless Steel (default)
A2 304 St/St with Equip. Tag
A4 316 St/St with Equip. Tag (304)
Product version: [v] A1 IECEx & ATEX Group II 2G/D Zone 1, 2, 21 & 22
Enclosure colour: [x] R Red RAL3000
Lens colour: [y] A
B
C
G
M
R
Y
Amber
Blue
Clear
Green
Magenta
Red
Yellow
Example part code: STExC1X05FAC230 [e][m][s][v][x]/[y]
STExC1X05FAC230AS2A1R/R

Coding

  • II 2G Ex db IIC Gb T6 Ta -50°C to +40°C
  • II 2G Ex db IIC Gb T5 Ta -50°C to +55°C
  • II 2G Ex db IIC Gb T4 Ta -50°C to +70°C
  • II 2D Ex tb IIIC Db T110°C Ta -50°C to +70°C

Effective Candela lens colour factor

 
Amber Blue Clear Green Red Yellow
0.70 0.24 1.00 0.25 0.23 0.93