D1xS2F Alarm Horn Sounder

125dB(A) alarm horn. The D1xS2F is a high output alarm horn sounder with re-entrant flare horn. Low current consumption and high SPL in a robust Type 4/4X, IP66 marine grade, corrosion proof aluminium enclosure ensure the D1xS2F is suitable for all Class I & II Division 1, Zone 1 & 20 explosion proof signaling applications. The 24V dc version is approved for public mode fire alarm use and the 110-240V ac version for general signaling use.

Featuring 64 alarm tone sounds, each of the available 4 stage/channels can be remotely triggered. Approved for gas groups ABCD in Class I Division 1, Class I Zone 1 IIC and for dust groups FG in Class II Division 1, Zone 20 IIIB environments. The threaded flameproof joint simplifies both installation and routine maintenance.

Specification

 
Maximum output: 125dB(A) @ 1 metre [116dB(A) @ 10ft/3m]
Nominal output: 121dB(A) @ 1m +/- 3dB - Tone 35 [112dB(A) @ 10ft/3m]
No. of tones: 64 (UKOOA / PFEER compliant)
No. of stages: 4
Volume control: Adjustable -12dB(A)
Effective range: 200m/656ft @ 1KHz
Voltages DC: 24V dc (10-30V dc)
Voltages AC: 110-240V ac 50/60Hz
Stage switching: DC units: negative or positive
AC units: common supply line
Ingress protection: EN60529: IP66
UL50E / NEMA250: 4 / 4X / 3R / 13
Enclosure material: Marine grade aluminium LM6- copper free
Chromated & powder coated - corrosion proof
Colour: Red (RAL3000), Grey (RAL7038)
Cable entries: 1 x 1/2"NPT & 2 x M20 x 1.5mm
1 x 1/2"NPT & 2 x 1/2"NPT
1 x 1/2"NPT & 2 x 3/4"NPT
Terminals: 0.5 - 2.5mm² (20-14 AWG)
Grounding stud: M5
Operating temp: -40° to +70°C [-40° to +158°F]
Storage temp: -50° to +70°C [-58° to +158°F]
Relative humidity: 95% - Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist
Weight: 4.3kg/9.5lbs

Part Codes

Version: Part code:
Product type: D1xS2
Horn type: F Flare re-entrant horn
Voltage: DC024
AC230
10-30V dc
110-240V ac
Cable Entry Type:[e] A
B
C
1 x 1/2"NPT & 2 x M20 x 1.5mm
1 x 1/2"NPT & 2 x 1/2"NPT
1 x 1/2"NPT & 2 x 3/4"NPT
Adaptor/Stopping
plug material: [m]
B
N
S
Brass
Nickel Plated
Stainless Steel
Bracket material: [s] 1
2
3
4
A2 304 Stainless Steel
A4 316 Stainless Steel
A2 304 St/St with Equip. Tag
A4 316 St/St with Equip. Tag (304)
Product version: [v] A1
D1
Gas environments Class I/Zone1
Dust environments Class II/Zone 20
Enclosure colour: [x] G
R
Grey RAL7038
Red RAL3000
Example: D1xS2FAC230 [e][m][s][v][x]
D1xS2FAC230AB1A1R
Ratings:
A1: Gas version
NEC / CEC: Class I Div 1 ABCD T6 Ta -40°C to +70°C
  Class I Div 2 ABCD T6 Ta -40°C to +70°C
  Class I Zone 1 IIC T6 Ta -40°C to +70°C
24V dc version is approved for public mode fire alarm use
D1: Dust version
NEC / CEC: Class II Div 1 FG T6 Ta -40°C to +70°C
  Class II Div 2 FG T6 Ta -40°C to +70°C
  Class III Div 1&2
  Zone 20 IIIB Ta -40°C to +70°C

Alarm sounder

Version: Voltage: Current:
10-30V dc 24V dc 923mA
110-240V ac 50/60Hz 115V ac 267mA
110-240V ac 50/60Hz 230V ac 159mA

Coding

  • A1: Gas version 
    NEC / CEC: 
    Class I Div 1 ABCD T6 Ta -40°C to +70°C 
    Class I Div 2 ABCD T6 Ta -40°C to +70°C 
    Class I Zone 1, 2 IIC T6 Ta -40°C to +70°C 
    24V dc version is approved for public mode fire alarm use
  • D1: Dust version 
    NEC / CEC: 
    Class II Div 1 FG T6 Ta -40°C to +70°C 
    Class II Div 2 FG T6 Ta -40°C to +70°C 
    Class III Div 1 & 2 
    Zone 20, 21, 22 IIIB Ta -40°C to +70°C
  • Protection concept: Ex d / AEx d