loa-den-chong-chay-no-bexcs110-05-bexcs110-05-explosion-proof-alarm-horn-xenon-strobe-e2s-vietnam-stc-vietnam.png

D1xC1X05R Radial Alarm Horn & Xenon Strobe

115dB(A) horn & 5 Joule Xenon. The D1xC1X05R is a high output alarm horn sounder with omni-directional radial horn combined with a 500,000cd Xenon strobe beacon. The robust Type 4/4X, IP66 marine grade, corrosion proof aluminium enclosure ensures the D1xC1X05R is suitable for all Class I & II Division 1, Zone 1 & 20 explosion proof signaling applications. The Class I DC version is approved for public mode fire alarm use (alarm horn) and private mode fire alarm use (strobe beacon).

The explosion proof horn strobe allows simultaneous or independent operation. Featuring 64 first stage/channel alarm sounds, the alarm tone frequencies for the first 2 stages are independently selectable. Each of the 4 stage/channels can be remotely triggered e.g. via an external relay.

Specification

 
Alarm Horn:
Maximum output: 115dB(A) @ 1 metre [106dB(A) @ 10ft/3m]
Nominal output: 110dB(A) @ 1m +/- 3dB - Tone 2 [101dB(A) @ 10ft/3m]
No. of tones: 64 (UKOOA / PFEER compliant)
No. of stages: 4
Volume control: Adjustable -12dB(A)
Effective range: 125m/410ft @ 1KHz
Supply Voltages: 24Vdc; 115Vac; 230Vac
Stage switching: DC units: negative or positive
AC units: common supply line
Strobe Beacon:
Energy: 5 Joules (5Ws)
Flash rates: Option 1: 1Hz (60 fpm)
Option 2: 1.5Hz (90 fpm)
Option 3: Double Strike
Peak Candela: 500,000 cd - calculated from energy (J)
Effective Intensity: 250 cd - calculated from energy (J)
Peak Candela: 46,976 cd* - measured ref. to I.E.S.
Effective Intensity: 143 cd* - measured ref. to I.E.S.
Lens colours: Amber, Blue, Clear, Green, Magenta, Red & Yellow
Tube life : Emissions are reduced to 70% after 8 million flashes
General:
Ingress protection: EN60529: IP66
UL50E / NEMA250: 4 / 4X / 3R / 13
Enclosure material: Marine grade aluminium LM6- copper free
Chromated & powder coated - corrosion proof
Colour: Red (RAL3000), Grey (RAL7038)
Cable entries: 1 x 1/2"NPT & 2 x M20 x 1.5mm
1 x 1/2"NPT & 2 x 1/2"NPT
1 x 1/2"NPT & 2 x 3/4"NPT
Terminals: 0.5 - 2.5mm² (20-14 AWG)
Grounding stud: M5
Operating temp: 24Vdc & 115Vac: -40° to +70°C [-40° to +158°F]
230Vac: -40° to +55°C [-40° to +131°F]
Storage temp: -50° to +70°C [-58° to +158°F]
Relative humidity: 95% - Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist
Weight: 4.9kg/10.9lbs

Current Consumption

Voltage: Range: Alarm Horn Xenon Strobe Combined
24V dc 20-28Vdc 217mA 322mA 539mA
115V ac 110-120Vac
50/60Hz
76mA 129mA 206mA
230V ac 220-240Vac
50/60Hz
53mA 79mA 132mA

Part Codes

Version: Part code:
Product type: D1xC1X05
Horn type: R Omni-directional radial horn
Voltage: DC024
AC115
AC230
20-28V dc
110-120V ac
220-240V ac
Cable Entry Type:[e] A
B
C
1 x 1/2"NPT & 2 x M20 x 1.5mm
1 x 1/2"NPT & 2 x 1/2"NPT
1 x 1/2"NPT & 2 x 3/4"NPT
Adaptor/Stopping
plug material: [m]
B
N
S
Brass
Nickel Plated
Stainless Steel
Bracket/Guard material: [s] 1
2
3
4
A2 304 Stainless Steel
A4 316 Stainless Steel
A2 304 St/St with Equip. Tag
A4 316 St/St with Equip. Tag (304)
Product version: [v] A1
D1
Gas environments Class I/Zone1
Dust environments Class II/Zone 20
Enclosure colour: [x] G
R
Grey RAL7038
Red RAL3000
Lens colour: [y] A, B, C, G
M, R, Y
Amber, Blue, Clear, Green
Magenta, Red, Yellow
Example: D1xC1X05RAC230 [e][m][s][v][x][y]
D1xC1X05RAC230AB1A1R/A
Ratings:
A1: Gas version
NEC / CEC: Class I Div 1 ABCD T5/T6 Ta -40°C to +70/+55°C
Class I Div 2 ABCD T5/T6 Ta -40°C to +70/+55°C
Class I Zone 1, 2 IIC T5/T6 Ta -40°C to +70/+55°C
D1: Dust version
NEC / CEC: Class II Div 1 FG T4/T4A Ta -40°C to +55/+40°C
Class II Div 2 FG T4/T4A Ta -40°C to +55/+40°C
Class III Div 1&2
Zone 20, 21, 22 IIIB T4/T4A Ta -40°C to +55/+40°C

Coding

  • A1: Gas version 
    NEC / CEC: 
    Class I Div 1 ABCD T5/T6 Ta -40°C to +70/+55°C 
    Class I Div 2 ABCD T5/T6 Ta -40°C to +70/+55°C 
    Class I Zone 1, 2 IIC T5/T6 Ta -40°C to +70/+55°C
  • D1: Dust version 
    NEC / CEC: 
    Class II Div 1 FG T4/T4A Ta -40°C to +55/+40°C 
    Class II Div 2 FG T4/T4A Ta -40°C to +55/+40°C 
    Class III Div 1 & 2 
    Zone 20, 21, 22 IIIB T4/T4A Ta -40°C to +55/+40°C
  • Protection concept: Ex d / AEx d

Effective Candela lens colour factor

 
Amber Blue Clear Green Red Yellow
0.70 0.24 1.00 0.25 0.23 0.93