loa-den-chong-tia-lua-d2xc2ld2-h-d2xc2ld2-horn-led-synchronized-ul464-ul1971-e2s-vietnam-stc-vietnam.png

D2xC2LD2-H Horn & LED Synchronized UL464 & UL1971

The haz loc D2xC2LD2-H is an auto-synchronizing alarm horn & LED light/beacon tested to UL464 & UL1971 suitable for public mode fire alarm, ADA compliant, hearing impaired applications. The unit is UL/cUL approved for Class I Div 2, Class II Div 2, Class I Zone 2/22 as well as IECEx and ATEX certified for Zone 2 and 22 hazardous area applications.

The D2xC2LD2-H utilises an array of high power Cree® LED's, orientated to optimise visibility in any direction. Multiple D2xC2LD2-H units will auto-synchronize when powered from the same power source removing the need for any additonal sync modules on the circuit. The horn & LED light can be powered from the same source, simplifying installation and reducing cabling costs. UL1971 effective candela rating of 38.38cd.

Specification

 
Alarm Horn Sounder:
Maximum output: 116dB(A) @ 1 metre [107dB(A) @ 10ft/3m]
Nominal output: 112dB(A) @ 1m +/- 3dB - Tone 2 [103dB(A) @ 10ft/3m]
No. of tones: 64 (UKOOA / PFEER compliant)
No. of stages: 4
Volume control: Adjustable -12dB(A) [Tone 2]
Effective range: 125m/410ft @ 1KHz
Synchronization All alarm tones synchronize
LED Beacon/Light:
Source: Array of 4 x High Power Cree® LED's
Modes: 1Hz flash (60 fpm)
1.3Hz flash (80 fpm)
2Hz flash (120 fpm
Eff. Intensity cd: 38.38 cd UL1971 Public mode fire
Eff. Intensity cd: 180 cd UL1638 General signaling
Peak Intensity cd: 300,000 cd
LED life: >60,000 hours
Synchronization: Flash rates synchronize for a minimum of 2 hours per UL1971
General:
Voltage: 24V dc [16-33V dc]
In rush: 2.1A for <10ms
Ingress protection: IP rating per EN60529:IP66
Type rating per UL50E/NEMA250:4/4X/3R/13
Enclosure material: Marine grade LM6 aluminum alloy
Enclosure colour: Red (RAL3000)
Lens material: Borosilicate glass
Cable entries: 2 x 1/2"NPT
Stopping plugs: Nickel Plated Brass plugs included
Ground/Earth stud: M5
Terminals: 0.5 - 2.5mm² (20-14 AWG)
Line monitoring: Blocking diode included
EOL can be factory fitted
Operating temp: -40 to +50°C [-40° to +122°F]
Storage temp: -40 to +70°C [-40° to +158°F]
Relative humidity: 95%
Weight: 4.00kg/8.82Ibs

Current Consumption

Nominal
Voltage:
Voltage
range:
Flash
Rate
setting:
Nominal
current
[Beacon]:
Nominal
current
[Alarm Horn]:
 

24V dc

Regulated
16-33V dc
1Hz (60fpm)
1.3Hz (80 fpm)
2Hz (120fpm)
99.5mA
104mA
103mA

313mA

Part Codes

Part Code: Ident.: Description:
Product type: D2xC2LD2 Combination Alarm Horn & LED Beacon/Light
Voltage: DC024 24V dc (16-33Vdc)
Cable entries: [e] B 2 x 1/2” NPT
Stopping plug material: [m] N Nickel plated brass
Lens Guard: [s] 0 No lens Guard
Version: [v] H1 UL, cUL, IECEx & ATEX - UL1971
Enclosure: [x] R Red RAL3000
Lens colour: [y] C Clear
e.g: D2xC2LD2DC024BN0H1R/C D2xC2LD2-H LED Beacon, 24Vdc
nickel plated brass stopping plugs,
UL, cUL, IECEx & ATEX approved - UL1971
Red enclosure with Clear lens
Also available as the D2xB1LD2-H LED standalone beacon see www.e2s.com/1-31-060

Coding

  • NEC / CEC: Class I Div 2 ABCD T2B Ta -40°C to +70°C 
    Class I Div 2 ABCD T4 Ta -40°C to +50°C 
    Class I Div 2 ABCD T4A Ta -40°C to +40°C 
    Class II Div 2 EFG T6 Ta -40°C to +50°C 
    Class III Div 1&2 Ta -40°C to +50°C 
  • NEC: Class I Zone 2 AEx nA IIC T4 Gc (Ta -40°C to +50°C) 
    AEx tc IIIC 75°C Dc Ta -40°C to +50°C 
  • CEC: Class I Zone 2 Ex nA IIC Gc T4 Ta -40°C to +50°C 
    Zone 22 Ex tc IIIC 75°C Dc Ta -20°C to +55°C 
  • IECEx & ATEX: II 3G Ex nA IIC T4 Gc Ta -40°C to +50°C 
    II 3D Ex tc IIIC 75°C Dc Ta -40°C to +50°C

Multi-function patterns

Stage 1:
[On board]
Stage 2:
[Remote]
Stage 3:
[Remote]
 
Steady High Power Flashing 1Hz † Triple Strike
Steady Low Power Flashing 1Hz † Triple Strike
Flashing 1Hz † 2x Flash 2Hz Triple Strike
Flashing 1.3Hz † Flashing 2Hz † Double Strike
Flashing 2Hz † Triple Strike Triple Strike
Double Strike Steady High Power Triple Strike
Triple Strike Flashing 2Hz † Double Strike
† Setting permitted for use as public mode fire alarm device