loa-den-chong-tia-lua-d2xc2xh2-d2xc1x10-horn-xenon-strobe-synchronised-ul464-ul1971-e2s-vietnam-stc-vietnam.png

D2xC2XH2 Horn & Xenon Strobe Synchronised UL464 & UL1971

The D2xC2XH2 is a 63.73cd auto-synchronizing alarm horn & Xenon light/beacon tested to UL464 & UL1971 suitable for public mode fire alarm, ADA compliant, hearing impaired applications. The unit is UL/cUL approved for Class I Div 2, Class II Div 2, Class I Zone 2/22 as well as IECEx and ATEX certified for Zone 2 and 22 hazardous area applications.

Multiple D2xC2XH2 units will auto-synchronize when powered from the same power source removing the need for any additional sync modules in the circuit. The horn & strobe can be powered from the same source, simplifying installation and reducing cabling costs.

Specification

 
Alarm Horn Sounder:
Maximum output: 116dB(A) @ 1 metre [107dB(A) @ 10ft/3m]
Nominal output: 112dB(A) @ 1m +/- 3dB - Tone 2 [103dB(A) @ 10ft/3m]
No. of tones: 64 (UKOOA / PFEER compliant)
No. of stages: 4
Volume control: Adjustable -12dB(A) [Tone 2]
Effective range: 125m/410ft @ 1KHz
Synchronization All alarm tones synchronize
Xenon Strobe Beacon/Light:
Source: Xenon Strobe
Modes: 1Hz flash (60 fpm)
1.3Hz flash (80 fpm)
1.5Hz flash (90fpm)
Double flash
Eff. Intensity cd: 63.73 cd UL1971 Public mode fire
Peak Candela: 1,000,000 cd - calculated from energy (J)
Effective cd: 500 cd - calculated from energy (J)
Synchronization: Flash rates synchronize for a minimum of 2 hours per UL1971
General:
Voltage: 24V dc [20-28V dc]
In rush: 2.3A for 9ms
Ingress protection: IP rating per EN60529:IP66
Type rating per UL50E/NEMA250:4/4X/3R/13
Enclosure material: Marine grade LM6 aluminum alloy
Enclosure colour: Red (RAL3000)
Lens material: Borosilicate glass
Cable entries: 2 x 1/2"NPT
Stopping plugs: Nickel Plated Brass plugs included
Ground/Earth stud: M5
Terminals: 0.5 - 2.5mm² (20-14 AWG)
Line monitoring: Blocking diode included
EOL can be factory fitted
Operating temp: -40 to +50°C [-40° to +122°F]
Storage temp: -40 to +70°C [-40° to +158°F]
Relative humidity: 95%
Weight: 4.00kg/8.82Ibs

Current Consumption

Nominal
Voltage:
Voltage
range:
Nominal
operating
current:
24V dc 20-28V dc 759mA
In-rush: 2.3A within 9ms

Part Codes

Part Code: Ident.: Description:
Product type: D2xC2XH2 Combination Alarm Horn & Xenon Beacon/Light
Voltage: DC024 24V dc (20-28Vdc)
Cable entries: [e] B 2 x 1/2” NPT
Stopping plug material: [m] N Nickel plated brass
Lens Guard: [s] 0 No lens Guard
Version: [v] H1 UL, cUL, IECEx & ATEX - UL1971
Enclosure: [x] R Red RAL3000
Lens colour: [y] C Clear
e.g: D2xC2XH2DC024BN0H1R/C D2xC2XH2 Horn & Xenon, 24Vdc
nickel plated brass stopping plugs,
UL, cUL, IECEx & ATEX approved - UL1971
Red enclosure with Clear lens
Also available as the D2xB1XH2 standalone beacon see www.e2s.com/1-31-080

Coding

  • NEC / CEC: Class I Div 2 ABCD T2A Ta -40°C to +50°C 
    Class II Div 2 FG T6 Ta -40°C to +50°C 
    Class III Div 1&2 Ta -40°C to +50°C 
  • NEC: Class I Zone 2 AEx nA IIC T2 Gc (Ta -40°C to +50°C) 
    AEx tc IIIC 85°C Dc Ta -40°C to +50°C 
  • CEC: Ex nA IIC T2 Gc X Ta -40°C to +50°C 
    Ex tc IIIC 85°C Dc Ta -40°C to +50°C 
  • IECEx & ATEX: II 3G Ex nA IIC T2 Gc Ta -40°C to +50°C 
    II 3D Ex tc IIIC 85°C Dc Ta -40°C to +50°C