Loa đèn chống tia lửa E2xC1X05R, E2xC1LD2F Combination Radial Alarm Horn & Xenon Strobe E2S Vietnam, STC Vietnam
Hãng sản xuất: Nex Flow
Ứng dụng sản phẩm: Sắt thép, gỗ, Thực phẩm, thủy tinh, bao bì, bia, rượu, xi măng,dệt may,dầu khí,sx ô tô, cơ khí...
E2xC1X05R Combination Radial Alarm Horn & Xenon Strobe
The hazardous location E2xC1X05R combined alarm sounder and Xenon strobe beacon is UL/cULs approved for Class I Div 2 and Class II Div 2 as well as IECEx and ATEX certified for Zone 2 and 22 applications.
The E2xC1X05R combines a 114dB(A) alarm sounder with a 5 Joule Xenon strobe beacon providing a complete audio-visual signalling solution whilst reducing the installation time and costs associated with multiple unit installations.
The E2x range features enclosures manufactured from lightweight, corrosion proof PPS and high impact, fire retardant ABS radial horns (providing omnidirectional sound dispersion); both of which are suitable for the harshest of environments.
Specification
Alarm Horn Sounder: | |
Maximum output: | 114dB(A) @ 1 metre [105dB(A) @ 10ft/3m] |
Nominal output: | 110dB(A) @ 1m +/- 3dB - Tone 2 [102dB(A) @ 10ft/3m] |
No. of tones: | 45 (UKOOA/PFEER compliant) |
No. of stages: | 3 |
Volume control: | Max. 113dB(A) Min. 105dB(A) - Tone 2 |
Effective range: | 100m/328ft @ 1KHz |
Xenon Strobe Beacon: | |
Energy: | 5 Joules (5Ws) |
Flash rate: | 1Hz (60 fpm) |
Peak Candela: | 500,000 cd - calculated from energy (J) |
Effect. Intensity cd: | 250 cd - calculated from energy (J) |
Peak Candela: | 34,122 cd* - measured ref. to I.E.S. |
Effective Intensity cd: | 108 cd* - measured ref. to I.E.S. |
Lens colours: | Amber, Blue, Clear, Green, Magenta, Red & Yellow |
General: | |
Voltages: | 24vdc; 48vdc; 115vac; 230vac |
Ingress protection: | IP rating per EN60079-0:IP64 IP rating per EN60529:IP66 Type rating per UL50E/NEMA250:4/4X/13 |
Enclosure material: | UL94V0 PPS & ABS |
Lens material: | Borosilicate glass dome with PC prismatic lens cover. |
Guard: | Stainless Steel dome guard as standard |
Cable entries: | Dual M20x1.5 or 1/2"NPT |
Terminals: | 0.5 - 2.5mm² (20-14 AWG) |
Line monitoring: | Blocking diode included EOL can be factory fitted |
Operating temp: | -20 to +55°C [-4° to +131°F] |
Storage temp: | -40 to +70°C [-40° to +158°F] |
Relative humidity: | 90% at 20°C [68°F] |
Weight: | DC: 3.00Kg/6.6Ibs AC: 3.50kg/7.7Ibs |
* All candela data is representative of performance with clear lens at optimum voltage. |
Current Consumption
Alarm Sounder | Xenon Beacon | |||
---|---|---|---|---|
Version: | Voltage: | Current: | Voltage: | Current |
24V dc | 10-30V dc | 284mA | 20-28V dc | 275mA |
48V dc | 38-58V dc | 146mA | 42-58V dc | 145mA |
115V ac 50/60Hz |
+/-10% | 104mA | +/-10% | 80mA |
230V ac 50/60Hz |
+/-10% | 54mA | +/-10% | 30mA |
*Candela measurements representative of performance with clear lens at optimum voltage. SPL readings are at nominal voltage, typically +/-3dB and are for indication purposes only. Where applicable, reduce outputs by 5dB when a 10-30vdc unit is supplied 12vdc. |
Part Codes
Part Code: | Ident.: | Description: | |
---|---|---|---|
Product type: | E2xC1X05 | Combined alarm horn & Xenon | |
Type: | R | Radial omni-directional horn | |
Voltage: | AC115 AC230 DC012 DC024 DC048 |
115V ac 50/60Hz 230V ac 50/60Hz 12V dc (10-14Vdc) 24V dc (20-28Vdc) 48V dc (42-54Vdc) |
|
Cable entries:[e] | A B C |
M20x1.5 & ½” NPT M20x1.5 & M20x1.5 ½” NPT & ½” NPT |
|
Stopping plug material: [m] | N | Nylon | |
Bracket & Guard: [s] | 1 2 |
304 (A2) Stainless Steel 316 (A4) Stainless Steel |
|
Version: [v] | A1 | UL, cULs, IECEx & ATEX | |
Enclosure: [x] | B | Black | |
Lens colour: [y] | A, B, C G, M, R Y |
Amber, Blue, Clear Green, Magenta, Red Yellow |
|
NOTE: | The E2xC1X05 supersedes the E2xCS112-5, maintaining compatibility with existing installations. |
Coding
- ATEX / IECEx certification
II 3G Ex nA IIC T3 Gc Ta -20°C to +40°C
II 3G Ex nA IIC T2 Gc Ta -20°C to +55°C
II 3D Ex tc IIIC 85°C Dc Ta -20°C to +40°C
II 3D Ex tc IIIC 100°C Dc Ta -20°C to +55°C - NEC Class / Zone ratings US
Class I Zone 2 AEx nA IIC T3 Gc Ta -20°C to +40°C
Class I Zone 2 AEx nA IIC T2 Gc Ta -20°C to +55°C
Zone 22 AEx tc IIIC 85°C Dc Ta -20°C to +40°C
Zone 22 AEx tc IIIC 100°C Dc Ta -20°C to +55°C - CEC Class / Zone ratings Canada
Ex nA IIC T3 Gc Ta -20°C to +40°C
Ex nA IIC T2 Gc Ta -20°C to +55°C
Ex tc IIIC 85°C Dc Ta -20°C to +40°C
Ex tc IIIC 100°C Dc Ta -20°C to +55°C - NEC & CEC Class / Division Ratings for US / Canada
Class I, Div 2, ABCD T2D Ta -20°C to +55°C
Class I, Div 2, ABCD T3 Ta -20°C to +40°C
Class II, Div 2, FG T5 Ta -20°C to +55°C
Class II, Div 2, FG T6 Ta -20°C to +40°C
Class III, Div 1&2 Ta -20°C to +55°C