loa-den-chong-chay-no-d1xc1x05f-bexcs110-05-alarm-horn-xenon-strobe-e2s-vietnam-stc-vietnam.png

D1xC1X05F Alarm Horn & Xenon Strobe

117dB(A) horn & 5 Joule Xenon. The D1xC1X05F is a high output alarm horn sounder with re-entrant flare horn combined with a 500,000cd Xenon strobe beacon. The robust Type 4/4X, IP66 marine grade, corrosion proof aluminium enclosure ensures the D1xC1X05F is suitable for all Class I & II Division 1, Zone 1 & 20 explosion proof signaling applications. The Class I DC version is approved for public mode fire alarm use (alarm horn) and private mode fire alarm use (strobe beacon). The AC versions are suitable for general signaling.

The alarm horn & Xenon strobe allow simultaneous or independent operation. Featuring 64 first stage/channel alarm sounds, the alarm tone frequencies for the first 2 stages are independently selectable. Each of the 4 stage/channels can be remotely triggered e.g. via an external relay.

Specification

 
Alarm Horn:
Maximum output: 117dB(A) @ 1 metre [108dB(A) @ 10ft/3m]
Nominal output: 113dB(A) @ 1m +/- 3dB - Tone 2 [104dB(A) @ 10ft/3m]
No. of tones: 64 (UKOOA / PFEER compliant)
No. of stages: 4
Volume control: Adjustable -12dB(A)
Effective range: 125m/410ft @ 1KHz
Supply Voltages: 24Vdc; 115Vac; 230Vac
Stage switching: DC units: negative or positive
AC units: common supply line
Strobe Beacon:
Energy: 5 Joules (5Ws)
Flash rates: Option 1: 1Hz (60 fpm)
Option 2: 1.5Hz (90 fpm)
Option 3: Double Strike
Peak Candela: 500,000 cd - calculated from energy (J)
Effective Intensity: 250 cd - calculated from energy (J)
Peak Candela: 46,976 cd* - measured ref. to I.E.S.
Effective Intensity: 143 cd* - measured ref. to I.E.S.
Lens colours: Amber, Blue, Clear, Green, Magenta, Red & Yellow
Tube life : Emissions are reduced to 70% after 8 million flashes
General:
Ingress protection: EN60529: IP66
UL50E / NEMA250: 4 / 4X / 3R / 13
Enclosure material: Marine grade aluminium LM6- copper free
Chromated & powder coated - corrosion proof
Colour: Red (RAL3000), Grey (RAL7038)
Cable entries: 1 x 1/2"NPT & 2 x M20 x 1.5mm
1 x 1/2"NPT & 2 x 1/2"NPT
1 x 1/2"NPT & 2 x 3/4"NPT
Terminals: 0.5 - 2.5mm² (20-14 AWG)
Grounding stud: M5
Operating temp: 24Vdc & 115Vac: -40° to +70°C [-40° to +158°F]
230Vac: -40° to +55°C [-40° to +131°F]
Storage temp: -50° to +70°C [-58° to +158°F]
Relative humidity: 95% - Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist
Weight: 5.2kg/11.4lbs

Current Consumption

Voltage: Range: Alarm Horn Xenon Strobe Combined
24V dc 20-28Vdc 217mA 322mA 539mA
115V ac 110-120Vac
50/60Hz
76mA 129mA 206mA
230V ac 220-240Vac
50/60Hz
53mA 79mA 132mA

Part Codes

Version: Part code:
Product type: D1xC1X05
Horn type: F Flare re-entrant horn
Voltage: DC024
AC115
AC230
20-28V dc
110-120V ac
220-240V ac
Cable Entry Type:[e] A
B
C
1 x 1/2"NPT & 2 x M20 x 1.5mm
1 x 1/2"NPT & 2 x 1/2"NPT
1 x 1/2"NPT & 2 x 3/4"NPT
Adaptor/Stopping
plug material: [m]
B
N
S
Brass
Nickel Plated
Stainless Steel
Bracket/Guard material: [s] 1
2
3
4
A2 304 Stainless Steel
A4 316 Stainless Steel
A2 304 St/St with Equip. Tag
A4 316 St/St with Equip. Tag (304)
Product version: [v] A1
D1
Gas environments Class I/Zone1
Dust environments Class II/Zone 20
Enclosure colour: [x] G
R
Grey RAL7038
Red RAL3000
Lens colour: [y] A, B, C, G
M, R, Y
Amber, Blue, Clear, Green
Magenta, Red, Yellow
Example: D1xC1X05FAC230 [e][m][s][v][x][y]
D1xC1X05FAC230AB1A1R/A
Ratings:
A1: Gas version
NEC / CEC: Class I Div 1 ABCD T5/T6 Ta -40°C to +70/+55°C
Class I Div 2 ABCD T5/T6 Ta -40°C to +70/+55°C
Class I Zone 1, 2 IIC T5/T6 Ta -40°C to +70/+55°C
D1: Dust version
NEC / CEC: Class II Div 1 FG T4/T4A Ta -40°C to +55/+40°C
Class II Div 2 FG T4/T4A Ta -40°C to +55/+40°C
Class III Div 1&2
Zone 20, 21, 22 IIIB T4/T4A Ta -40°C to +55/+40°C

Coding

  • A1: Gas version 
    NEC / CEC: 
    Class I Div 1 ABCD T5/T6 Ta -40°C to +70/+55°C 
    Class I Div 2 ABCD T5/T6 Ta -40°C to +70/+55°C 
    Class I Zone 1, 2 IIC T5/T6 Ta -40°C to +70/+55°C
  • D1: Dust version 
    NEC / CEC: 
    Class II Div 1 FG T4/T4A Ta -40°C to +55/+40°C 
    Class II Div 2 FG T4/T4A Ta -40°C to +55/+40°C 
    Class III Div 1 & 2 
    Zone 20, 21, 22 IIIB T4/T4A Ta -40°C to +55/+40°C
  • Protection concept: Ex d / AEx d

Effective Candela lens colour factor

 
Amber Blue Clear Green Red Yellow